24kV Indoor Switchgear Earthing Switch With Sensor
Dongfa Intelligent supplies 24kV indoor switchgear earthing switches with sensors for switchgear builders handling 24kV maintenance grounding. Rated 1.5kA/1s with 3.75kA making capacity and integrated sensor posts, it reduces live-closing risks. Request a quote for CAD drawings and pricing.
In-Cabinet Assembly Details: Why Integrated Sensor Posts Save Panel Space
Looking at the actual installation inside a 24kV Aluzinc-coated switchgear enclosure, the layout of the DFES1.5-24 earthing switch is straightforward and compact. Three red shedded epoxy resin insulator posts stand aligned on the base frame, with voltage-indicating sensor structures built directly into the upper post heads (110×190mm profile on the CAD drawing). In space-restricted 24kV cubicles, integrating the sensor into the post eliminates separate sensor mounting brackets and prevents extra high-voltage leads from crowding internal creepage clearances.
The grounding current path is also clearly separated from mechanical pivot joints. Moving blades use conductive copper bars paired with galvanized steel brackets (261.5±1.5mm closed height per pole), while a crimped bare braided copper strap connects from the base terminal (15mm mounting hole height) straight to the main earth busbar. Directing fault current through the braided strap keeps current out of the main shaft and hinges, preventing arc pitting or mechanical binding. On the right-hand side, a spring-assisted linkage crank drives all three poles together so closing action stays crisp and synchronized.
Engineering Meaning Behind the Ratings: Fault Stress, Insulation, and Endurance
When reviewing technical specs for a 24kV indoor switchgear earthing switch with sensor, the rated numbers point directly to specific grid stresses:
Parameter
Rated Specification
Practical Engineering Meaning
Rated Voltage / Frequency
24kV / 50Hz
Matches standard 20kV–24kV medium-voltage indoor distribution panels
Rated Short-Time Withstand Current (1s)
1.5kA
Defines the 1-second thermal boundary of the earth path without blade welding or distortion
Rated Short-Circuit Making Current (Peak)
3.75kA peak
Measures the ability to close against electromagnetic forces if a line is accidentally energized
Holds up against switching surges and lightning impulses with added open-gap clearance
Phase-to-Phase Distance
230mm
Fits common 24kV air-insulated switchgear bay widths
Mechanical Endurance Class
M1
Covers routine maintenance earthing cycles over a switchgear panel's service life
In real operation, the 3.75kA peak making rating matters whenever induced voltage or human error leaves a circuit live during earthing. Adequate spring force and contact clamp pressure keep the blades from bouncing or welding on impact. Meanwhile, the 50kV/60kV power-frequency and 125kV/145kV impulse ratings establish clear dielectric separation both to the grounded frame and across the open air gap.
Panel Mounting Dimensions and Shop-Floor Verification
Panel builders lose valuable assembly time when mounting holes miss cross-beam centers by even a few millimeters. According to the DFES1.5-24 CAD layout, the base frame measures 818mm in overall width and 806mm in shaft length, with 720mm left-to-right mounting hole centers and 60mm front-to-back centers on a 170.5mm wide mounting plate. Pole centers sit at 230mm intervals (98mm from the left edge to the first pole), with a 121mm closed blade projection and 78.5mm shaft center distance. If your cubicle uses a non-standard phase pitch or requires a modified operating shaft length, Dongfa Intelligent adjusts dimensions to your panel drawings and supports trial orders starting from 1 unit.
With over 14 years of experience manufacturing medium-voltage switchgear and core components in Yueqing, Dongfa Intelligent builds every 24kV indoor switchgear earthing switch with sensor under ISO 9001 quality controls. Before dispatch, technicians check three-pole closing synchronization, verify main circuit resistance, and run dielectric withstand tests in line with GB/T 1985 and IEC 62271-102 requirements so panels arrive ready for smooth commissioning.
Specification for Earthing Switch 1.5kA
Name of Product: Earthing Switch 24kV 1.5kA
Type: DFES1.5-24
Test Category:
Standard:
No.
Description
Abbreviation
Unit
Specification
1
Brand
-
-
DFZN
2
Type
-
-
DF ES1.5-24
3
Rated voltage
Ur
kV
24
4
Rated frequency
fr
Hz
50
5
Rated lightning impulse withstand voltage
Up
kV
125
6
Rated lightning impulse withstand voltage (kV) peak (Across the isolating distance)
Up
kV
145
7
Rated short-duration power-frequency withstand voltage (kV)
Ud
kV
50
8
Rated short-duration power-frequency withstand voltage (kV) (Across the isolating distance)
Ud
kV
60
9
Rated short-time withstand current
Ik
kA
1.5
10
Rated short-circuit making current (kA) Peak
Ip
kA-peak
3.75
11
Rated duration of short-time withstand current (s)
tk
s
1
12
Mechanical endurance class (MI/M2/M3)
-
-
M1
13
Phase to phase distance
-
mm
230
14
Overall dimension
-
mm
14
Standard
-
-
Dimension Drawing
Field Feedback and Buyer Questions
"We installed Dongfa Intelligent's 24kV earthing switches in a commercial switchgear project in the UAE. Having the sensors built right into the red insulator posts saved wiring space inside the compartments, the 720mm mounting holes lined up cleanly, and the panels cleared local utility inspection without issues."
— Tariq M., Engineering Supervisor at a UAE Medium-Voltage Switchgear Builder
Can this 24kV earthing switch be supplied for left-hand operation?
Yes. The standard CAD drawing places the operating linkage on the right side when viewed from the front, but we can reverse the shaft orientation and match your panel's interlock hole location during assembly.
Do the top sensor posts work with standard voltage-indicating devices?
Yes. The integrated capacitive sensor posts are designed to connect with standard 24kV indoor live-line indicators and electromagnetic interlock circuits. Share your indicator model so we can confirm secondary terminal compatibility.
Can we order 1 unit first for prototype cubicle fitting?
Yes. Standard 230mm phase-spacing units are available from 1 piece so your engineering team can verify mechanical fitment and interlocking before volume production.