Follow Us:

Products
24kV 20kA High Fault Rating Indoor Earthing Switch
  • 24kV 20kA High Fault Rating Indoor Earthing Switch24kV 20kA High Fault Rating Indoor Earthing Switch

24kV 20kA High Fault Rating Indoor Earthing Switch

Dongfa Intelligent supplies 24kV 20kA high fault rating indoor earthing switches for switchgear builders handling high-fault 24kV panels. Rated 20kA/1s with 50kA peak making capacity and phase barrier shrouds, it supports heavy busbar grounding safety. Request a quote for CAD drawings and pricing.
    24kV 20kA High Fault Rating Indoor Earthing Switch

    High-Fault 24kV Switchgear Demands: Why 20kA Construction Differs

    In utility feeder bays, industrial main substations, and heavy-load 24kV distribution panels, fault levels run much higher than in light branch switchgear. If a line is accidentally energized when the earthing switch closes, tens of kiloamperes of fault current create heavy electromagnetic forces and thermal stress that can bend blades or weld contacts on lighter switches.

    Dongfa Intelligent builds this 24kV 20kA indoor earthing switch (factory type DFES20-24, matching the JN15-24/20 frame layout) for 20kA short-time withstand and 50kA peak making duties. It pairs dependable earthing with phase barrier shrouds to help contain flashover risks inside compact enclosures.

    Structural Breakdown From Cabinet Photos and Drawings

    Looking at the in-cabinet installation photo alongside the engineering drawings shows how this 20kA design handles heavy closing forces and tight panel spaces:

    Three-Sided Phase Barrier Shrouds: Each pole head carries a red epoxy resin U-shaped shroud with side slots. Inside a 24kV enclosure, these barriers add physical separation between phases during switching arcs or induced fault events.

    Dual-Side Compression Spring Drive: Unlike single-sided spring arrangements, heavy compression spring assemblies sit on both ends of the base frame (736mm center-to-center spring span). When released, the springs drive the copper earthing blades (280mm contact height, 380mm overall height) firmly into engagement to resist contact bounce under a 50kA peak make.

    Dedicated Braided Copper Earth Path: The operating shaft runs across the three-pole frame (806mm total shaft length with a 20×20mm square / Φ20mm end), while a crimped bare braided copper strap routes earthing current to the main earth connection instead of forcing heavy fault current through shaft bearings.

    Key Ratings and What They Mean on Heavy Feeders

    When reviewing 24kV switchgear specifications, rated values tie directly to real system stress:

    Parameter Rated Specification Practical Engineering Meaning
    Rated Voltage / Frequency 24kV / 50Hz Matches standard 20kV–24kV medium-voltage indoor switchgear systems
    Rated Short-Time Withstand Current (1s) 20kA Defines thermal endurance during a 1-second 20kA earth fault without blade welding or distortion
    Rated Short-Circuit Making Current (Peak) 50kA peak Indicates ability to close against high electromagnetic repulsion if a circuit is live
    Power-Frequency Withstand Voltage (1min) 50kV (to earth) / 60kV (across isolating distance) Provides higher insulation margin across open contacts during maintenance
    Lightning Impulse Withstand Voltage 125kV (to earth) / 145kV (across isolating distance) Handles impulse and switching surges with extra open-gap dielectric margin
    Phase-to-Phase Distance 230mm Fits standard 24kV air-insulated switchgear phase spacing
    Mechanical Endurance Class M1 Covers routine maintenance earthing operations over switchgear service life

    CAD Mounting Dimensions and Quality Control

    Because a 20kA earthing switch has larger springs and shrouds than light-duty models, checking clearance against busbars and cable compartments before fabrication saves rework. Based on the DFES20-24 drawing (in millimeters):

    Base and Depth Dimensions: 810mm base width (806mm shaft length) and 376mm front-to-back depth (328.5mm from rear mounting edge to insulator centerline, 108.5mm from shaft centerline to insulator centerline, and 45mm shaft centerline height).

    Pole and End Spacing: 230mm phase-to-phase centers, 168.5mm from the left edge to the first pole center, 188.5mm from the right insulator center to the shaft tip, 280mm contact center height, and 380mm overall height.

    Custom Fitment and Testing: Dongfa Intelligent manufactures under ISO 9001 controls and GB/T 1985 and IEC 62271-102 standards. Every unit goes through spring release checks, three-pole closing alignment, loop resistance verification, and power-frequency withstand testing before dispatch, with orders starting from 1 unit and shaft/spacing adjustments available to your drawings.

    Earthing Switch 24kV 20kA

    Specification for Earthing Switch 20kA

    Name of Product: Earthing Switch 24kV 20kA

    Type: DFES20-24

    Test Category:

    Standard:

    No. Description Abbreviation Unit Specification
    1 Brand - - DFZN
    2 Type - - DF ES20- 24
    3 Rated voltage Ur kV 24
    4 Rated frequency fr Hz 50
    5 Rated lightning impulse withstand voltage Up kV 125
    6 Rated lightning impulse withstand voltage (kV) peak (Across the isolating distance) Up kV 145
    7 Rated short-duration power-frequency withstand voltage (kV) Ud kV 50
    8 Rated short-duration power-frequency withstand voltage (kV) (Across the isolating distance) Ud kV 60
    9 Rated short-time withstand current Ik kA 20
    10 Rated short-circuit making current (kA) Peak Ip kA-peak 50
    11 Rated duration of short-time withstand current (s) tk s 1
    12 Mechanical endurance class (MI/M2/M3) - - M1
    13 Phase to phase distance - mm 230
    14 Overall dimension - mm
    15 Standard - -

    Dimension Drawing

    Earthing Switch 24kV 20kA

    Customer Feedback and Common Questions

    "We used Dongfa Intelligent's 20kA earthing switches on a 22kV industrial substation project in Saudi Arabia. The dual-spring closing action felt solid, the phase shrouds were sturdy, and the 376mm depth fit our 24kV panels cleanly through third-party witness testing."

    — Hassan K., Chief Project Engineer at a Saudi Switchgear Manufacturer

    Can the 20kA model replace a 1.5kA earthing switch using the exact same cabinet cutouts?

    Both use 230mm phase spacing, but the 20kA DFES20-24 adds dual heavy spring drives and top phase shrouds, changing base width (810mm vs. 818mm), depth (376mm), and height (380mm). Always check your compartment layout against the 20kA CAD drawing before cutting brackets.

    Is the operating shaft on the right side by default, and can it be set to the left?

    The standard drawing places the operating shaft end (20×20mm square / Φ20mm) on the right. If your panel interlock sits on the left, let us know when ordering so we can configure left-hand operation during assembly.

    Can we order 1 unit first for sample testing or prototype assembly?

    Yes. Standard 230mm phase-spacing units can be ordered starting from 1 piece with inspection records and dimensional drawings included.

    Send Inquiry
    Contact Info
    Contact Dongfa Intelligent for electrical products. We welcome your inquiry and will provide product details, pricing and technical support.
    X
    We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
    RejectAccept